Siemens FC724-ZA 4 LOOP Analog Control Unit Fire Detection System S54400-C30-A2
Siemens FC724-ZA 4 LOOP analog control panel, Cerberus PRO fire detection system, up to 504 addresses, network configurable, with the following features:
-
Loops supported: 4 (expandable to 8)
-
C-NET Addresses: Max 504
-
Stub lines: Up to 16 with extension
-
Power supply: AC 115/230 V ±10/-15 %, 150 W
-
Emergency Runtime: Up to 72 h
-
Interfaces: 2x RS232/RS485, 1x RJ45, 2 module slots
-
Outputs: 2 alarm, 2 fault, 2 monitored siren
-
Free Inputs/Outputs: 12 configurable
-
Degree of protection: IP30
Siemens FC724-ZA control panel: advanced and scalable fire detection
The FC724-ZA analog control panel is the heart of Siemens' Cerberus PRO fire detection system. Compact, powerful and fully configurable, it is designed to manage up to 504 devices addressed on 4 C-NET loops, with expansion capability up to 8 loops or 16 stubs (with additional modules).
The system supports networking of up to 64 stations (central or terminal), providing coverage of large buildings, business complexes or hospital facilities.
Cerberus PRO technology: reliability and automation
Compatible with FD720 detectors, the central station enables automatic detection and self-configuration of C-NET devices, with remote upload/download, programmable commands and centralized event management (up to 13,000).
It is equipped with advanced features such as timed switching of parameter sets, degraded function, monitored outputs for alarm, fault and siren, RS232/RS485 slot, and Ethernet interface for network management.
Functional features and optional configurations
In addition to the basic unit, several optional modules are available such as:
-
Event printer
-
Key switches (Kaba or Nordic)
-
Additional LED units
-
Single-zone shutdown module
The control unit can be programmed locally or via PC, adapting to any system requirements.
Recommended applications
-
Public buildings and industrial complexes
-
Hospitals, airports, shopping malls
-
Critical infrastructure and data centers
-
Facilities requiring integrated control center network
Technical Specifications Siemens analog control unit
| Parameter | Value |
|---|---|
| Loops supported | 4 (expandable to 8) |
| C-NET Addresses | Max 504 |
| Stub lines | Up to 16 with extension |
| Compatibility | FD720 detectors (Cerberus PRO) |
| Network configuration | Up to 64 panels/terminals |
| Shutdown | Optional integrated single zone |
| Interfaces | 2x RS232/RS485, 1x RJ45, 2 module slots |
| Outputs | 2 alarm, 2 fault, 2 monitored siren |
| Free inputs/outputs | 12 configurable |
| Power supply | AC 115/230 V ±10/-15 %, 150 W |
| Batteries | 2x 12 V, max 25 Ah |
| Emergency autonomy | Up to 72 h |
| Operating temperature | -8 °C TO +42 °C |
| Max. relative humidity | ≤95% (without condensation) |
| Dimensions with cover | 443 x 802 x 188 mm (WxHxD) |
| Degree of protection | IP30 |
| Standards | EN 54 - with integrated degraded function |
| Remote configuration | Cerberus Engineering Tool |
| Cloud Connectivity | Cloud for Buildings Siemens |
| Display | User-friendly with integrated control unit |
Data sheet
- Type: Fire alarm systems
- Zone: 4