Siemens motor protection circuit breaker S2 42-52A 65KA 3RV20314WA10


SIE 3RV20314WA10 4011209945715

Siemens thermomagnetic circuit breaker/reversing switch , with the following characteristics:

  • Insulation voltage with pollution degree 3 with AC nominal value 690 V
  • Rated impulse withstand voltage 6 kV
  • Rated operational voltage 690 V
  • Operating current nominal value 52A
  • Adjustable tripping value for current-dependent overload release current 42 ...52A
  • Short-circuit breaking capacity (Ics) at AC 65 kA
  • 3 poles
  • 2.5 modules
Request info about this product

Siemens motor protection circuit breaker S2 42-52A 65KA 3RV20314WA10

€209.77
€209.77

Siemens motor protection circuit breaker S2 42-52A 65KA 3RV20314WA10

€209.77
Tax included
klarna Pay in installments with Klarna
Out of stock Incoming
qty

Siemens motor protection circuit breaker S2 42-52A 65KA 3RV20314WA10

€209.77

Two-year warranty
Secure Payment
Easy return within 14 days

The motor protection switch is installed on the cable that feeds the motor and, when the motor stops due to a mechanical effect or (in three-phase systems) because a phase is missing, it detects an excessive absorption and automatically cuts off the electrical energy, thus safeguarding the integrity of the motor.

Features:

  • Siemens series
  • Insulation voltage with pollution degree 3 with AC nominal value 690 V
  • Rated impulse withstand voltage 6 kV
  • Rated operational voltage 690 V
  • Frequency of use nominal value 50/60 Hz
  • Operating current nominal value 52A
  • Adjustable tripping value for current-dependent overload release current 42 ...52A
  • Power loss at nominal AC current value in warm state 24.5W - in AC in warm state per pole 8.2W
  • Design size S2
  • Shock resistance according to IEC 60068-2-27 25g / 11 ms
  • Mechanical service life (switching cycles) of main contacts typ 100,000 - of auxiliary contacts typ 100,000
  • Installation altitude for altitude above sea level max 2000 m
  • Ambient temperature during operation -20/+60 °C - during storage -50/+80 °C - during transport -50/+80 °C
  • Temperature compensation -20 ... +60 °C
  • Relative humidity during operation 10 ... 95 %
  • 3 poles
  • 2, 5 modules
  • Short-circuit breaking capacity (Ics) at AC 65 kA
  • Degree of protection on front side IP20
  • Any mounting position
  • Type of mounting screw and snap-on mounting on 35 mm DIN-rail
  • Height 140 mm
  • Width 55 mm
  • Depth 149 mm
  • Tightening torque for main contacts with screw terminals 0.8 ... 1.2 Nm
  • Design of screwdriver shank Diameter 5...6 mm
  • Screwdriver tip size Pozidriv 2

Data sheet

Type:
Motor protection
Modules:
2.5
Poles:
3P
Breaking capacity:
65KA
Amps:
42-52A