Telemecanique 1.6-2.5A 2.5 Modules Circuit Breaker GV2ME07
Schneider TeSys GV2 Telemecanique motor-saving circuit breaker, with the following characteristics:
- Number of poles: 3P
- Network type: AC
- Utilization category: AC-3 complying with IEC 60947-4-1, Category A complying with IEC 60947-2
- Mains frequency: "50/60 Hz" complying with IEC 60947-4-1
- Mounting type, 35 mm symmetrical DIN rail: hooked, Panel: screwed (with adapter plate)
- Control type: Pushbutton
- Rated current [In]: 2.5 amps
- Thermal protection control range: 1.6 to 2.5 A in accordance with IEC 60947-4-1
- Magnetic release current: 33.5 A
- Conventional thermal current in air [Ith]: 2.5 A complying with IEC 60947-4-1
Telemecanique 1.6-2.5A 2.5 Modules Circuit Breaker GV2ME07
Tax included
Frequently bought together
GV2ME07 is a TeSys GV circuit breaker from Schneider Electric for motors. It provides thermal-magnetic protection of 0.75 kW motors at 400 V and high breaking capacity Icu 100 kA. Push-button start-stop control guaranteed for 100,000 cycles AC-3 415V. GV2ME07 is a TeSys GV motor circuit breaker from Schneider Electric designed for 0.75 kW motor applications at 400 V. It meets thermal-magnetic protection with a 1.6-2.5 A thermal control range, 12 xIn magnetic trip and high breaking capacity Icu 100 kA at 400 V. Push-button start-stop control guaranteed for 100,000 cycles AC-3 415V. Available worldwide, has certification to various standards (IEC, UL, CSA, CCC, EAC, for use in marine environments) and is Green Premium (RoHS/REACH) compliant.
Advantages:
- Complete motor protection in one device: short circuit, overload, disconnection
- Combined with a TeSys contactor, it ensures a complete starte type 1 or 2 motor solution
- Lightweight and compact, 45 mm wide, for DIN rail and panel mounting
- Manual control with push buttons for Start / Stop, padlockable
- Possible mounting of auxiliary contacts at front or side for status and trip signaling
Motor power in kW:
- 0.75 kW at 400/415 V "AC" "50/60 Hz"
- 1.1 kW at 500 V "AC" "50/60 Hz"
- 1.5 kW at 690 V "AC" "50/60 Hz"
Interrupting capacity:
- 100 kA Icu complying with IEC 60947-2 at 230/240 V AC 50/60 Hz
- 100 kA Icu complying with IEC 60947-2 at 400/415 V AC 50/60 Hz
- 100 kA Icu complying with IEC 60947-2 at 440 V AC 50/60 Hz
- 100 kA Icu complying with IEC 60947-2 at 500 V AC 50/60 Hz
- 3 kA Icu complying with IEC 60947-2 at 690 V AC 50/60 Hz
Rated service interrupting capacity [Ics]:
- 100 % complying with IEC 60947-2 at 500 V AC 50/60 Hz
- 100 % complying with IEC 60947-2 at 230/240 V AC 50/60 Hz
- 100 % complies with IEC 60947-2 at 440 V AC 50/60 Hz
- 100 % complying with IEC 60947-2 to 400/415 V AC 50/60 Hz
- 75 % compliant with IEC 60947-2 at 690 V AC 50/60 Hz
Other technical characteristics:
- Rated use voltage [Ue]: 690 V AC 50/60 Hz complying with IEC 60947-2
- Rated insulation voltage [Ui]: 690 V AC 50/60 Hz complying with IEC 60947-2
- Rated impulse withstand voltage [Uimp]: 6 kV complying with IEC 60947-2
- Phase failure sensitivity: Yes complying with IEC 60947-4-1
- Disconnection capability: Yes complying with IEC 60947-1 § 7-1-6
- Energy dissipation per pole: 2.5 W
- Mechanical life: 100000 cycles
- Electrical life: 100000 cycles for AC-3 at 415 V In
- Rated service: Continuous in accordance with IEC 60947-4-1
- Tightening torque: 1.7 Nm - on screw clamp
- Width 45 mm
- Height 89 mm
- Depth 78.5 mm
- Weight 0.26 kg
- Color: dark gray
- Degree of protection IK: IK04
- IP degree of protection: IP20 in accordance with IEC 60529
- Climatic sealing: complies with IACS E10
- Storage temperature: -40/+80 °C
- Fire resistance: 960 °C complying with IEC 60695-2-11
- Ambient temperature: -20/+60 °C
- Mechanical robustness: Shock: 30 gn for 11 ms - Vibration: 5 gn, 5...150 Hz
- Operating altitude: Acti9 iCV40 ARC
Data sheet
- Type:
- Motor protection
- Voltage:
- 690V
- Poles:
- 3P
- Degree of protection:
- IP20