Double Insulated Flameproof Cable FG16OR16 4x1.5mmq 0.6/1 kV Grey FG16R4X1.5M
Double insulated flame-resistant FG16OR16 cable, designed to ensure safety and efficiency, ideal for indoor and outdoor electrical installations. With its PVC flame-retardant jacket and ethylene-propylene rubber insulation, it offers fire resistance and excellent electrical performance, with the following characteristics:
-
Section: 4x1.5 sq. mm
-
Conductor diameter: 1.6 mm
-
Insulation thickness: 0.7 mm
-
Sheath thickness: 1.8 mm
-
Outer diameter: 11.2 mm
-
Electrical resistance: 13.3 ohm/km
-
Current carrying capacity: 19.5A in air tube, 19A in buried tube
-
Rated voltage: 0.6/1 kV
-
Suitable for: Fixed laying in air, pipe or conduit and also for underground laying
The selling price is per meter.
Sold by 100-metre hank only.
- Baldassari cavi
- Icel
- La Triveneta
- Prysmian
The minimum purchase order quantity for the product is 100.
The minimum purchase order quantity for the product is 100.
FG16OR16 cable: reliable, versatile and high-performance
CPR-certified reliability and safety
This multi-core cable complies with the Construction Products Regulation (CPR), ensuring reduced smoke emission and flame spread in case of fire.
Suitable for indoor and outdoor installations
Thanks to the AD7 degree of protection, it can be installed in wet environments, inside civil or industrial buildings and structures, offering versatility and high performance even in harsh conditions.
Excellent electrical performance
With a maximum electrical resistance of 13.3 ohm/km and a current carrying capacity of up to 19.5A in air tube, the cable ensures efficiency and reliability in all types of installations.
Technical Specifications FG16OR16 Flameproof Cable
| Feature | Value |
|---|---|
| Conductor | Flexible annealed red copper cord, class 5 |
| Insulator | High-modulus ethylpropylene rubber compound of G16 quality |
| Filler | Compound of nonhygroscopic material |
| Outer sheath | PVC compound of R16 quality |
| Sheath color | Gray |
| Rated voltage Uo/U | 0.6/1 kV |
| Maximum operating temperature | 90 degrees |
| Minimum operating temperature | -15 degrees |
| Minimum laying temperature | 0 degrees |
| Maximum short circuit temperature | 250°C up to 240 mm², above 220°C |
| Maximum tensile stress | 50 N/mm² |
| Minimum bending radius | 4 times maximum outer diameter |
| Conductor diameter | 1.6 mm |
| Insulation thickness | 0.7 mm |
| Sheath thickness | 1.8 mm |
| Outer diameter | 11.2 mm |
| Max. electrical resistance at 20°C | 13.3 ohm/km |
| Current flow rate in air tube | 19,5 A |
| Current flow rate in buried pipe | 19 A |
Data sheet
- Colour: Grey
- Cross-Section: 1.5mmq
- With yellow/green: No
- Number of cables: 4
: 1000