CPR FS18OR18 2x1.5 sq. mm 450/750V flame-resistant cable


9X9 FS18OR182X1,5BV7

CPR FS18OR18 2x1.5 sq mm 450/750V flame-proof cable with the following characteristics:

  • Conductor diameter: 1.5 mm
  • Insulation thickness: 0.4 mm
  • Sheath thickness: 1 mm
  • Production diameter: 6.6 mm
  • Maximum electrical resistance at 20°: 13.3 ohms/km
  • Current carrying capacity at 30° in air tube: 22A

The selling price is per meter.

The producers of our cables are:

  • Baldassari cavi
  • Icel
  • La Triveneta
  • Prysmian
The delivery of the cable from one manufacturer rather than another is dictated by the availability of the moment. All our cables comply with the relevant legal regulations.  
The right of withdrawal does not apply to this product as the cables are cut according to your personal specifications.
Request info about this product

CPR FS18OR18 2x1.5 sq. mm 450/750V flame-resistant cable

€0.58
€0.58

CPR FS18OR18 2x1.5 sq. mm 450/750V flame-resistant cable

€0.58
Tax included
klarna Pay in installments with Klarna
qty

CPR FS18OR18 2x1.5 sq. mm 450/750V flame-resistant cable

€0.58

Buy it within and receive it from Tuesday, 14 May
Two-year warranty
Secure Payment

FS18OR18 cables belong to the AFIAM line and are marked Cca-s3,d1,a3, to indicate that they are compliant with the Construction Products Regulation (CPR) in accordance with the requirements prescribed in EN 50575:2014+A1:2016 and to indicate that they are of the non-fire-propagating type in accordance with the self-extinguishing requirements prescribed in IEC EN 50399 in whose tests heat emission, smoke production and possible dripping during the flame development test are also measured.

FS18OR18 cables are also flame-retardant on the single vertical cable as per EN and IEC 60332-1-2 (IEC 20-35) tests. In addition, to prevent further hazards from substances emitted during combustion of plastics, FS18OR18 cables are made of special halogen-reduced compounds, with the amount of hydrochloric acid, contained in the fumes emitted during combustion, less than 18%.

FS18OR18 cables belong to the ecological line called ECOGAMMA marked by the Windmill symbol. Lead, a heavy metal that is dangerous to the environment and to humans if present in excessive quantities, has been eliminated in these environmentally friendly cables.

Energy, signaling, and control cable, insulated with S18-quality PVC under R18-quality PVC sheathing, with special fire reaction characteristics and meeting the Construction Products Regulation (CPR).

Characteristics:

  • Conductor: Flexible annealed red copper cord, class 5
  • Insulation: PVC compound of S18 quality
  • Outer sheath: R18-quality PVC compound
  • Sheath color: Brown
  • Rated voltage Uo/U: 450/750V
  • Maximum operating temperature: 70°C
  • Minimum operating temperature: -15°C (in the absence of mechanical stress)
  • Minimum installation temperature: 0°C
  • Maximum short-circuit temperature: 160°C
  • Maximum tensile stress: 50 N/mm2
  • Minimum bending radius: 4 times the maximum outer diameter


Conditions of use: Suitable for fixed laying or temporary installation in places with fire hazards. For indoor use in dry or wet rooms.

Data sheet

Cross-Section:
1.5mmq
With yellow/green:
Yes
Number of cables:
2