Telemecanique Contactor TeSys D 4P 40A AC1 220VAC LC1DT40M7

Schneider
SNR LC1DT40M7 3389110577709

Schneider TeSys D Telemecanique contactor, with the following characteristics:

  • Rated use voltage [Ue]: <= 690V "AC" 25...400 Hz Power circuit: <= 300V DC Power circuit.
  • Rated use current [Ie]: 40 A 60 °C) "AC" AC-1 for Power circuit at <= 440V
  • Control circuit type: AC at "50/60 Hz"
  • Control voltage [Uc]: 220V "AC" "50/60 Hz"
  • Number of poles: 4
  • Power pole contact composition: 4 NO
  • Auxiliary contact composition: 1 NO + 1 NC
  • Rated impulse withstand voltage [Uimp]: 6 kV complying with IEC 60947
  • Overvoltage category: Acti9 VigiARC iC40
  • Conventional open air thermal current [Ith]: 10A at <60 °C for signaling circuit, 40A at <60 °C for power circuit
Do you have questions about this product or did you not find what you were looking for? Ask us!
Telemecanique Contactor TeSys D 4P 40A AC1 220VAC LC1DT40M7
€78.80
€78.80

€78.80
Tax included
Calculate shipping cost

€78.80

Buy it within and receive it from Wednesday, 24 December
Two-year warranty
Easy return within 14 days

Other Specifications:

  • Rated interrupting capacity: 450A at 440 V per Power Circuit in accordance with IEC 60947
  • Average impedance: 2 mOhm "50 Hz" - Ith 40 A per Power Circuit
  • Electrical endurance: 1.4 Mccycles 40 A AC-1 at Ue <= 440V
  • Power dissipation per pole: 3.2 W AC-1
  • Operation time: 4...19 ms opening, 12...22 ms closing
  • Safety Reliability Level: B10d = 1369863 cycles Contactor with rated load in accordance with EN/ISO 13849-1, B10d = 20000000 cycles Contactor with mechanical load in accordance with EN/ISO 13849-1
  • Mechanical life span: 15 Mccycles
  • Maximum operating speed: 3600 cycles/h at <60 °C
  • Coil technology: without integrated suppressor module
  • VA inrush power: 70 VA 60 Hz 0.75 20 °C), 70 VA "50 Hz" 0.75 20 °C)
  • VA holding power consumption: 7.5 VA 60 Hz 0.3 20 °C), 7 VA "50 Hz" 0.3 20 °C)
  • Heat dissipation: 2 to 3 W at "50/60 Hz"
  • Auxiliary contact type: Mechanically linked type 1 NO + 1 NC complying with IEC 60947-5-1, mirror contact type 1 NC complying with IEC 60947-4-1
  • Signaling circ. frequency: 25...400 Hz
  • Minimum switching current: 5 mA per signaling circuit
  • Minimum switching voltage: 17V per signaling circuit
  • No-overlap time: 1.5 ms upon deactivation between NC and NO contact, 1.5 ms upon activation between NC and NO contact
  • Insulation resistance: > 10 MOhm per signaling circuit
  • IP degree of protection: IP20 Front side complies with IEC 60529
  • Climatic sealing: Conforms to IACS E10, complies with IEC 60947-1 Annex Q category D
  • Protection treatment: TH complying with IEC 60068-2-30
  • Pollution degree: 3
  • Operating ambient temperature: -40/+60 °C - 60/+70 °C with derating
  • Storage temperature: -60/+80 °C
  • Operating altitude: 0 to 3000 m
  • Fire resistance: 850 °C in accordance with IEC 60695-2-1
  • Height 91 mm
  • Width 45 mm
  • Depth 99 mm
  • Weight: 0.425 kg


Mechanical robustness:

  • Open contactor vibration: 2 Gn, 5...300 Hz
  • Closed contactor vibrations: 4 Gn, 5...300 Hz
  • Closed contactor shocks: 15 Gn for 11 ms
  • Contactor shocks open: 8 Gn for 11 ms

Control circuit voltage limits:

  • 0.3...0.6 Uc -40...70 °C "AC" de-energizing 50/60 Hz
  • 0.8...1.1 Uc -40...60 °C operating "AC" 50 Hz
  • 0.85...1.1 Uc -40...60 °C operating "AC" 60 Hz
  • 1...1.1 Uc 60...70 °C operating "AC" 50/60 Hz


Connections-clamps:

  • Control circuit: screw clamp terminals 2 cables 1...2.5 mm²flexible with cable termination
  • Control circuit: screw clamp terminals 1 wire 1...4 mm²flexible without cable termination
  • Control circuit: screw terminals 2 cables 1...4 mm²flexible without cable termination
  • Control circuit: screw terminals 1 wire 1...4 mm²flexible with cable termination
  • Control circuit: screw terminals 1 cables 1...4 mm²solid without cable termination
  • Control circuit: screw terminals 2 cables 1...4 mm²solid without cable termination
  • Power circuit: connector 1 cable 2.5...10 mm²flexible without cable termination
  • Power circuit: connector 2 cables 2.5...10 mm²flexible without cable termination
  • Power circuit: connector 1 cable 2.5...10 mm²flexible with cable termination
  • Power circuit: connector 2 cables 2.5...10 mm²flexible with cable termination
  • Power circuit: connector 1 cable 2.5...16 mm²solid without cable termination
  • Power circuit: connector 2 cables 2.5...16 mm²solid without cable termination

Tightening torque:

  • Control circuit: 1.7 Nm - on EverLink connectors for BTR screws - with Ø 6 mm flat screwdriver
  • Control circuit: 1.7 Nm - on EverLink connectors for BTR screws - with Philips screwdriver No 2
  • Power circuit: 1.7 Nm - on EverLink connectors for BTR screws - with Ø 6 mm flat screwdriver
  • Power circuit: 1.7 Nm - on EverLink connectors for BTR screws - with Philips screwdriver No 2
  • Control circuit: 1.7 Nm - on EverLink connectors for BTR screws - with pozidriv screwdriver No 2
  • Power circuit: 2.5 Nm - on EverLink connectors for BTR screws - with pozidriv screwdriver No 2
  • On EverLink connectors for BTR screws

Rated insulation voltage [Ui]:

  • 600 V CSA certified Power circuit:
  • 600 V UL certified Power circuit:
  • 690 V complying with IEC 60947-1 signaling circuit
  • 600 V CSA certified signaling circuit:
  • 600 V UL certified Signaling circuit:
  • 690 V complying with IEC 60947-4-1 Power circuit.

Rated allowable short-time withstand current [Icw]:

  • 50 A at <40 °C - 10 min per Power Circuit
  • 120 A at <40 °C - 1 min per Power Circuit
  • 240 A at <40 °C - 10 s per Power Circuit
  • 380 A at <40 °C - 1 s per Power circuit
  • 100 A - 1 s per signaling circuit
  • 120 A - 500 ms per signaling circuit
  • 140 A - 100 ms per signaling circuit

Associated fuse gauge:

  • 10 A gG per signaling circuit in accordance with IEC 60947-5-1
  • 63 A gG at <= 690 V coordination Type 1 for Power circuit
  • 40 A gG at <= 690 V coordination Type 2 for Power circuit

Rated closing power Irms:

  • 140A "AC" for signaling circuit complying with IEC 60947-5-1
  • 250A DC for signaling circuit complying with IEC 60947-5-1
  • 450A at 440 V for Power circuit complying with IEC 60947

Data sheet

Type:
Contactors
Voltage:
220VAC
Poles:
4P
Degree of protection:
IP20
Amps:
40A