4Power Uninterruptible Power Supply UPS Third Power Plus 4000 4KVA THPPMM400010T
UPS 4Power Third Power Plus 4000 (THPPMM400010T) On-Line double conversion 4kVA/4kW: cos? 1, PFC, zero transfer time and advanced battery management for total protection of servers and critical loads.
-
Topology: On-Line double conversion
-
Classification: VFI-SS-II2
-
Rated power: 4000 VA
-
Active power: 4000 W (inverter cos= 1)
-
Input voltage: 208/220/230/240 V selectable (1Ph+N), 50/60 Hz
-
Output voltage: 208/220/230/240 V selectable (1Ph+N)
-
Input stage: IGBT rectifier with PFC (input cos 0.99)
-
Transfer time: 0 ms (On-Line)
-
Functions: Cold Start, ABM, EPO, ACB, neutral test, battery test, auto restart
-
By-pass: automatic + provision for external manual by-pass
-
Communication: RS232/USB, SNMP slot, supervision/shutdown software included
-
Interface: Interactive LCD display
-
Batteries: Hot Swap (hot replacement)
-
Data line protection: telephone/fax/modem
-
Extended autonomy: up to 3 hours with external battery packs (variable).
UPS 4Power Third Power Plus 4000 real continuity for critical loads
The UPS 4Power Third Power Plus 4000 4kVA (THPPMM400010T) is designed to ensure continuity and quality of power supply where even a minimal interruption is unacceptable. The double conversion On-Line technology ensures that the load is always powered by the inverter, maintaining stable voltage and a perfectly sinusoidal waveform. In case of blackout or disturbances (micro interruptions, overvoltages, undervoltages), the UPS completely isolates the user from the network: the result is total protection for sensitive equipment and IT infrastructures.
Efficiency and network quality: PFC and IGBT for superior performance
This model integrates an IGBT rectifier with input PFC, designed to reduce the impact on the electrical network and improve energy efficiency. The input power factor can reach values ≥ 0.99, contributing to cleaner absorption and more efficient consumption management. Furthermore, the inverter with cos? = 1 allows the full use of available power: 4000VA corresponds to 4000W, a tangible advantage when powering servers, storage, network devices, or loads with significant demands.
Professional battery management: ABM, Hot Swap, and Cold Start
To reduce costs over time and increase reliability, the Third Power Plus series integrates advanced functions such as A.B.M. (Automatic Battery Management), battery tests, and A.C.B. alerts for replacement. The Cold Start function allows startup even in the absence of a network, while Hot Swap Battery allows battery replacement on the fly (where installation permits), limiting system downtime. Auto Restart automatically restarts the UPS when the network returns after a complete discharge, useful in remote or unattended sites.
Monitoring and integration: LCD, RS232/USB, and SNMP
The interactive LCD display offers immediate reading of status and parameters. For integration into IT systems, RS232/USB ports, an SNMP card slot, and supervision/shutdown software for major operating systems are available. In professional environments, these functions help manage alarms, controlled shutdowns, and energy reports.
Recommended applications: IT, LAN, medical, and small industry
This UPS is ideal for servers, LAN networks, professional PCs, telecommunication devices, and medical equipment, as well as small industrial users. With external battery packs, it can provide up to 3 hours of autonomy (depending on load and configuration), covering even prolonged network absence scenarios.
| GENERAL DATA | |
|---|---|
| Model | THPP4000 |
| Product code | THPPMM400010T |
| Nominal power | 4000 VA |
| Active power | 4000 W |
| INPUT | |
| Input voltage | 208 V / 220 V / 230 V / 240 V (1Ph+N) selectable |
| Voltage variation range | from 110 to 300 Vac |
| Nominal frequency | 40 – 70 Hz (autosensing) |
| Accepted frequency variation | ±5 Hz |
| Input power factor | ≥ 0.99 (THD < 2%) |
| OUTPUT | |
| Nominal voltage | 208 V / 220 V / 230 V / 240 V (1Ph+N) selectable |
| Voltage stability | ±1% |
| Nominal frequency | 50 / 60 Hz ±0.1% (battery mode) |
| Waveform | Sinusoidal |
| Harmonic distortion | ≤ 2% T.H.D. with linear load |
| Crest factor | 3 : 1 |
| AC/AC efficiency | > 95% |
| Intervention time | Zero – On-line double conversion |
| Overload capacity (25 °C) | <150% Pn for 30 s / >150% Pn for 1 s |
| BATTERIES | |
| Type | VRLA AGM |
| Battery voltage | 192 / 240 Vdc |
| Capacity | 7 Ah |
| Recharge time | 6 – 8 h |
| Autonomy (80% / 50% load) | 10 min / 15 min |
| COMMUNICATION AND PROTECTIONS | |
| Telephone / LAN protection | RJ45 filter (10Base-T) |
| Communication interfaces | RS232 / USB |
| DIMENSIONS AND WEIGHT | |
| Dimensions (W × D × H) | 191 × 465 × 711 mm |
| Weight | 51 kg |
| ENVIRONMENTAL CONDITIONS | |
| Operating temperature | 0 ÷ 40 °C (max RH 90%) |
| Altitude / Relative humidity | Up to 3500 m / <95% non-condensing |
| COMPLIANCE AND CERTIFICATIONS | |
| EMC standards | Directive 2004/108/EC – EN 62040-2:2006, EN 61000-6-1-3:2007 |
| Safety standards (LVD) | Directive 2006/95/EC – EN 62040-1:2008, EN 62040-3:2002 |
| Marking | CE |
Data sheet
- Type: Uninterruptible Power Supply UPS
- Rated Power: 4000VA
- Active Power: 4000W
- Endurance: 10 minutes
15 minutes
: 1