4Power Uninterruptible Power Supply UPS Third Power Plus 4000 4KVA THPPMM400010T

4power
4PW THPPMM400010T

UPS 4Power Third Power Plus 4000 (THPPMM400010T) On-Line double conversion 4kVA/4kW: cos? 1, PFC, zero transfer time and advanced battery management for total protection of servers and critical loads.

  • Topology: On-Line double conversion

  • Classification: VFI-SS-II2

  • Rated power: 4000 VA

  • Active power: 4000 W (inverter cos= 1)

  • Input voltage: 208/220/230/240 V selectable (1Ph+N), 50/60 Hz

  • Output voltage: 208/220/230/240 V selectable (1Ph+N)

  • Input stage: IGBT rectifier with PFC (input cos 0.99)

  • Transfer time: 0 ms (On-Line)

  • Functions: Cold Start, ABM, EPO, ACB, neutral test, battery test, auto restart

  • By-pass: automatic + provision for external manual by-pass

  • Communication: RS232/USB, SNMP slot, supervision/shutdown software included

  • Interface: Interactive LCD display

  • Batteries: Hot Swap (hot replacement)

  • Data line protection: telephone/fax/modem

  • Extended autonomy: up to 3 hours with external battery packs (variable).

Do you have questions about this product or did you not find what you were looking for? Ask us!
4Power Uninterruptible Power Supply UPS Third Power Plus 4000 4KVA THPPMM400010T
€1,712.88
€1,712.88

€1,712.88
Tax included
Calculate shipping cost

€1,712.88

Buy it within and receive it from Friday, 26 December
Two-year warranty
Easy return within 14 days

UPS 4Power Third Power Plus 4000 real continuity for critical loads

The UPS 4Power Third Power Plus 4000 4kVA (THPPMM400010T) is designed to ensure continuity and quality of power supply where even a minimal interruption is unacceptable. The double conversion On-Line technology ensures that the load is always powered by the inverter, maintaining stable voltage and a perfectly sinusoidal waveform. In case of blackout or disturbances (micro interruptions, overvoltages, undervoltages), the UPS completely isolates the user from the network: the result is total protection for sensitive equipment and IT infrastructures.

Efficiency and network quality: PFC and IGBT for superior performance

This model integrates an IGBT rectifier with input PFC, designed to reduce the impact on the electrical network and improve energy efficiency. The input power factor can reach values ≥ 0.99, contributing to cleaner absorption and more efficient consumption management. Furthermore, the inverter with cos? = 1 allows the full use of available power: 4000VA corresponds to 4000W, a tangible advantage when powering servers, storage, network devices, or loads with significant demands.

Professional battery management: ABM, Hot Swap, and Cold Start

To reduce costs over time and increase reliability, the Third Power Plus series integrates advanced functions such as A.B.M. (Automatic Battery Management), battery tests, and A.C.B. alerts for replacement. The Cold Start function allows startup even in the absence of a network, while Hot Swap Battery allows battery replacement on the fly (where installation permits), limiting system downtime. Auto Restart automatically restarts the UPS when the network returns after a complete discharge, useful in remote or unattended sites.

Monitoring and integration: LCD, RS232/USB, and SNMP

The interactive LCD display offers immediate reading of status and parameters. For integration into IT systems, RS232/USB ports, an SNMP card slot, and supervision/shutdown software for major operating systems are available. In professional environments, these functions help manage alarms, controlled shutdowns, and energy reports.

Recommended applications: IT, LAN, medical, and small industry

This UPS is ideal for servers, LAN networks, professional PCs, telecommunication devices, and medical equipment, as well as small industrial users. With external battery packs, it can provide up to 3 hours of autonomy (depending on load and configuration), covering even prolonged network absence scenarios.

GENERAL DATA
Model THPP4000
Product code THPPMM400010T
Nominal power 4000 VA
Active power 4000 W
INPUT
Input voltage 208 V / 220 V / 230 V / 240 V (1Ph+N) selectable
Voltage variation range from 110 to 300 Vac
Nominal frequency 40 – 70 Hz (autosensing)
Accepted frequency variation ±5 Hz
Input power factor ≥ 0.99 (THD < 2%)
OUTPUT
Nominal voltage 208 V / 220 V / 230 V / 240 V (1Ph+N) selectable
Voltage stability ±1%
Nominal frequency 50 / 60 Hz ±0.1% (battery mode)
Waveform Sinusoidal
Harmonic distortion ≤ 2% T.H.D. with linear load
Crest factor 3 : 1
AC/AC efficiency > 95%
Intervention time Zero – On-line double conversion
Overload capacity (25 °C) <150% Pn for 30 s / >150% Pn for 1 s
BATTERIES
Type VRLA AGM
Battery voltage 192 / 240 Vdc
Capacity 7 Ah
Recharge time 6 – 8 h
Autonomy (80% / 50% load) 10 min / 15 min
COMMUNICATION AND PROTECTIONS
Telephone / LAN protection RJ45 filter (10Base-T)
Communication interfaces RS232 / USB
DIMENSIONS AND WEIGHT
Dimensions (W × D × H) 191 × 465 × 711 mm
Weight 51 kg
ENVIRONMENTAL CONDITIONS
Operating temperature 0 ÷ 40 °C (max RH 90%)
Altitude / Relative humidity Up to 3500 m / <95% non-condensing
COMPLIANCE AND CERTIFICATIONS
EMC standards Directive 2004/108/EC – EN 62040-2:2006, EN 61000-6-1-3:2007
Safety standards (LVD) Directive 2006/95/EC – EN 62040-1:2008, EN 62040-3:2002
Marking CE