Notifier Addressable module 2 inputs and 2 outputs CMA22


NOT CMA22

Notifier Addressable module 2 inputs and 2 outputs has two input channels for supervisory devices and firefighting devices with N.O. contacts and also has two outputs, one relay with potential-free contacts and one relay with potential-free or line-controlled contacts. This module on the analog line occupies four consecutive addresses , the installer must set in the rotary switches the first address. The first two addresses are dedicated to the input modules. The third address is dedicated to the output module with potential-free contacts.

Do you have questions about this product or did you not find what you were looking for? Ask us!
Notifier Addressable module 2 inputs and 2 outputs CMA22
€85.61
€85.61

€85.61
Tax included

€85.61

Two-year warranty
Easy return within 14 days

Strengths:

  • CPR certified in accordance with EN 54-18
  • Controlled input on supervised line
  • The second output can be controlled or with potential-free changeover contact, the first only with contact
  • Choice of output type is achieved by selecting two dip-switches
  • The module, using four consecutive addresses, is addressed by rotary switches numbered 01 to 99
  • These is equipped with four green and red LEDs that will give indications of the module's status
  • Power supply 15-32Vdc
  • Quiescent current of 620 microA and 860 microA with LED active
  • Operating temperature from 0 to +5°C
  • Relative humidity up to 93%

     

The module provides:

  • A two-color led indicating the status of the first input - Blinking green = no alarms and faults when the module is interrogated - Red= alarm condition from input
  • A two-color led indicating the status of the second input -Flashing green = absence of alarms and faults when the module is interrogated -Red= alarm condition from input
  • A two-color led indicating the status of the first output -Flashing green = absence of alarms and faults when the module is interrogated -Red= activation of 'output.
  • A two-color led indicating the status of the second output -Flashing green = absence of alarms and faults when the module is interrogated -Red= activation of the output

     

Features:

  • Supply voltage = 15Vdc ÷ 30Vdc (analog loop).
  • Quiescent current consumption @ 24Vdc (No communication) = 620uA
  • Current consumption (Communication with LED flashing) = 860uA
  • Ambient operating temperature = 0° C ÷ + 50° C
  • Relative humidity = 10% ÷ 93% (in the absence of condensation).