Earth terminal Cabur 6mm² yellow green
Earth terminal Cabur TEC Series code TO120, for TH35 rail, closed insulating body, same dimensions as CBC and GPA series:
-
With screw tightening
-
Impulse voltage / pollution degree: 8 kV / 3
-
Nominal section: 6 mm²
-
Colour: yellow/green
-
1 grounding plane
-
Mounting on DIN TH35 rail
-
Closed insulating body (no end plate required)
-
Dimensions: L 44 mm | H on TH35-7.5/15: 52 / 60 mm
-
Compatible dimensions with CBC and GPA series
-
Mounting: DIN TH35 rail
-
Insulating material: Polyamide UL94V-0
Earth terminal Cabur 6mm², reliability and safety for grounding
The Cabur earth terminal TEC Series TO120 is designed to ensure a safe, stable, and compliant ground connection in industrial and civil electrical installations. The closed insulating body enhances protection against accidental contact and simplifies installation, eliminating the need for the end plate.
The profile and dimensions identical to the CBC and GPA series allow perfect interchangeability in electrical panels, maintaining order and uniformity of wiring.
Wide connection capacity and reliable tightening
The screw tightening system ensures a stable electrical contact over time. The terminal supports flexible and rigid conductors from 0.5 to 10 mm², as well as conductors with terminal (model 6 mm² – WP60/20). The controlled tightening torque ensures reliability even in environments subject to vibrations.
UL, ATEX and IEC Ex compliance
The terminal complies with UL standards (up to 600 V AC/DC) and meets ATEX and IEC Ex requirements, with a nominal impulse voltage of 8 kV and pollution degree 3. The UL94V-0 polyamide insulating material ensures self-extinguishing and thermal resistance up to 130 °C (EN 60216-1).
| GENERAL DATA | |
|---|---|
| Function / Type | Earth terminal |
| Nominal section | 6 mm² |
| Gauge | A5 |
| CONNECTION CAPACITY | |
| Flexible conductor | 0.5 – 10 mm² |
| Rigid conductor | 0.5 – 10 mm² |
| Conductor with terminal | 6 mm² – WP60/20 |
| ELECTRICAL CHARACTERISTICS (UL) | |
| Maximum voltage AC/DC | 600 V |
| Maximum current with nominal section | 600 V |
| Section (min–max) | 24 – 8 AWG |
| Tightening torque (UL) | 15 lb·in |
| ELECTRICAL CHARACTERISTICS (ATEX / IEC Ex) | |
| Nominal impulse voltage / pollution degree | 8 kV / 3 |
| MECHANICAL CHARACTERISTICS | |
| Stripping length | 10 mm |
| Tightening torque (nominal / max.) | 0.8 / 1.4 Nm |
| Width (pitch) | 8 mm |
| Length | 44 mm |
| Height on TH35-7.5 / TH35-15 / G32 rail | 52 / 60 / – mm |
| MATERIALS | |
| Plastic material | Polyamide UL94 V-0 |
| Insulating material temperature index (EN 60216-1) | 130 °C |
Data sheet
- Colour: Yellow/Green
- Type: Clamps
- Cross-Section: 6mmq