Aluminium cable AUE4CR 3x10 + 6C 0.6/1 kV Grey for fixed installation


9X9 AUE4CR/3X10-6C

Cable AUE4CR 3x10 + 6C for fixed installation, XLPE insulated and PVC sheath, with the following characteristics:

  • Formation: 3x10 mm² + 6C

  • Conductor diameter: 3.5 mm

  • Insulation thickness: 0.7 mm

  • Sheath thickness: 2.2 mm

  • Max external diameter: 19 mm

  • Nominal voltage: 0.6/1 kV

  • ENEL registration number: 330566

The sale price is per metre.

The producers of our cables are:

  • Baldassari cavi
  • Icel
  • La Triveneta
  • Prysmian
The delivery of the cable from one manufacturer rather than another is dictated by the availability of the moment. All our cables comply with the relevant legal regulations.  
The right of withdrawal does not apply to this product as the cables are cut according to your personal specifications.
Depending on the length and/or diameter of the cable, transport may require the use of reels. This option involves an additional cost, which will be communicated upon completion of the order according to specific requirements.
Do you have questions about this product or did you not find what you were looking for? Ask us!
Aluminium cable AUE4CR 3x10 + 6C 0.6/1 kV Grey for fixed installation
€5.12
€5.12

€5.12
Tax included
Calculate shipping cost

€5.12

Buy it within and receive it from Monday, 9 February
Two-year warranty

Cable AUE4CR durable solution for LV systems

The cable AUE4CR 3 x 10 + 6C is designed for low voltage power transmission (0.6/1 kV), with three rigid aluminium conductors of 10 mm² and a concentric copper neutral conductor of 6 mm². Used in civil and industrial environments, it is suitable for fixed installation in ducts, pipes or directly buried, according to current regulations.

High-quality materials for long-term reliability

  • Conductors: Aluminium class 2 (3 x 10 mm²)

  • Concentric neutral: red copper wires with counter-spiral tape (6 mm²)

  • Sheath: Grey PVC quality Rz

Thanks to the combination of durable materials, this cable ensures excellent thermal, mechanical and electrical resistance, with reduced emission of toxic fumes in case of fire.

Versatile installation for indoor and outdoor environments

The cable is suitable for installation:

  • In air or wall-mounted tube

  • In duct or tray

  • Directly buried

The recommended minimum bending radius is 14 times the outer diameter of the cable (approximately 17 mm).

Technical Characteristics Aluminium cable AUE4CR

Nominal voltage Uo/U = 0.6/1 kV
Maximum operating temperature of phase conductors 90°C
Maximum operating temperature of concentric conductor 85°C
Minimum operating temperature –15°C
Maximum short circuit temperature Phases: 250°C – Neutral: 160°C
ENEL registration number 330566
Com-Cavi code 3492040100
Formation 3 × 10 + 6C mm²
Conductor Ø 3.5 mm
Insulation thickness 0.7 mm
Sheath thickness 2.2 mm
Max external Ø 19 mm
Cable weight 440 kg/km
Electrical resistance at 20°C 3.08 Ω/km
Current carrying capacity at 30°C In air: 60 A – In tube: 55 A – Buried: 71 A
Thermal short circuit current (1 s) Phases: 0.8 kA – Neutral: 0.8 kA

Data sheet

Colour:
Grey
Diameter:
19mm
Type:
Aluminum cables
Cross-Section:
10mmq
With yellow/green:
No
Number of cables:
3