Overvoltage arrester Finder 4 places 20kA 230/400 Vac 7P2482750020
FIN 7P2482750020
8012823398143
Finder overvoltage arrester, with the following characteristics:
- Rated voltage: 230V AC
- Rated continuous voltage: 275V AC, 255V DC
- Nominal voltage (remote contact) AC/DC 250/30V
- Nominal discharge current (8/20 μs) (In): 20 kA
- Maximum discharge current (8/20 μs) (Imax) 40 kA
- Rated current AC/DC (remote contact): 0.5/0.1
- SPD type 2 (3 varistors + 1 gas spark gap)
- Replaceable modules
- With remote contact for varistor status signalling
- SPD type 2 for three-phase TN-C systems without neutral (PEN)
- Varistor protection L1, L2, L3- PEN
- Replaceable varistor
- Contact configuration: 1 exchange
€98.38
€98.38
Items Available: 3
€98.38
Buy it within and receive it from Friday, 6 February
The surge protector, protects the entire system and what is connected to it, from surges, surges and peaks of electricity that may come from the operator, or from atmospheric phenomena such as lightning. These anomalies can cause serious damage to devices connected to the sockets such as breaking the hardware of a PC, or cause a short circuit to the boards of smartphones, tablets and household appliances.
Features:
- Finder Series
- Protection voltage level at 5 kA (UP5) 0.9 kV
- Protective voltage level at In(Up) 1.35/1.5 kV
- IPE uA: < 4
- TOV 120 min L-N: 440V AC
- TOV 5 s L-N 335V AC
- TOV 200 ms N-PE 1200V AC
- Trip time (ta) 25/100 ns
- Short circuit with maximum overcurrent protection - ISSCR kArm: 50
- Maximum overcurrent protection (fuse gL/gG): 160A
- Ambient temperature: - 40...+80°C
- Degree of protection IP20
- Connection capacity of solid wire terminals: 1 x 1...1 x 35mm2 - 1 x 17...1 x 2 AWG
- Connection capacity flexible wire terminals: 1 x 1...1 x 25 mm2 - 1 x 17...1 x 4 AWG
- Stripping length of cable 12 mm
- Tightening torque 3 Nm
Data sheet
- Maximum current: 40KA
- Version: 2
- Model: AC/DC
- Circuit Protections: Surge protectors
: 2