Gewiss Residual current device 25A 2P 30 mA AC type 2 modules GWD4617
Gewiss residual current device Series: 90 RCD, with the following characteristics:
- IDP NA abbreviation
- Pole numbers 2
- Numbers of modules 2
- Rated current 25 amps
- Rated differential current 30 mA
- Type AC
- Rated voltage (IEC/EN 61008-1, 61008-2-1) 230/240 V
- Reference standard IEC/EN 61008-1, IEC/EN 61008-2-1 Rated frequency (Hz) 50 Hz
- Insulation voltage 500 V Rated impulse withstand voltage 4 kV
- Overvoltage category III Immunity level (8/20µs wave) 250A
- Rigid cable section <=1x35 - <=2x16 - <=1x16+2x10 mm²
- Flexible cable section <=1x35 - <=2x16 - <=1x16+2x10 mm²
The residual current device is used to protect people, not systems. The moment the person goes to touch it, it creates a circuit with the ground. The current instead of staying in the household circuit, uses the human body to go to ground.
The residual current device is a device in your electrical system. It is capable of opening the circuit, that is, shutting off the power supply, the moment the current accidentally dissipates.
A residual current device offers protection in case of current leakage but not in case of overvoltage. Instead, the circuit breaker is required for this type of problem.
The AC-type earth leakage circuit breaker, works only with alternating current. Almost all systems for civil use fall into this type.
Other technical characteristics:
- Nominal tightening torque 2 Nm
- Biconconnection No
- Operating temperature -25 +60°C ( 40°C with derating)
- Storage temperature -40 +70°C
- Number of electrical maneuvers ≥ 5000
- Number of mechanical maneuvers ≥ 10,000
- Compatibility with electrical auxiliaries No Compatibility with ReStart Yes
- Mounting position Any
Data sheet
- Voltage: 230/240VAC
- Modules: 2
- Poles: 2P
- RCD Type: AC
- Differential current : 0.03A
- Amps: 25A
- Circuit Protections: Residual current devices
: 82