Abb DS201 C20 A300 Residual Current Circuit Breaker combines protection against overloads, short circuits and current leakage, ensuring safety and efficiency in electrical systems. Ideal for residential, commercial and industrial applications, with the following features:
-
Rated current: 20 amps
-
Number of poles: 2P
-
Tripping curve: C
-
Type of differential current: A (protects against unidirectional and pulsating leakage currents)
-
Rated residual current: 300 mA
-
Rated breaking capacity: 6 kA
-
Mounting: DIN rail for quick installation
-
Degree of protection: IP20/IP40
Abb Residual current circuit breaker 2P 20A 6kA C A 300mA 2M
The residual current circuit breaker offers dual protection:
-
Magnetothermal, which intervenes in the event of overloads and short circuits up to 6kA
-
Differential, which protects against current leakage above 300mA, preventing the risk of fire due to high leakage
Curve C provides optimal protection for circuits with moderate loads, such as lighting, electrical outlets, and small motors.
Versatility and Applications
Due to its compliance with safety standards and its ability to operate with a rated voltage of 230/440V, it is ideal for:
-
Residential installations (general system protection)
-
Commercial buildings (stores, offices, public places)
-
Industrial sector (switchboards, protection of circuits with high loads)
The 300mA differential protection makes it particularly suitable for preventing electrical fires in environments with older installations or where current leakage could pose a danger.
Compact Design and Simple Installation
The switch features a compact design with a width of 2 DIN modules (35mm), facilitating installation in electrical panels.
The IP20/IP40 degree of protection ensures resistance to dust and external agents, while the wide operating temperature range (-25/+55 degrees ) ensures reliable performance even under harsh conditions.
Key Features
| Feature | Value |
|---|---|
| Rated current | 20 A |
| Number of poles | 2P |
| Rated residual current | 300 mA |
| Rated short-circuit capacity | 6 kA |
| Input voltage type | A |
| Curve | C |
| Rated insulation voltage | 230/440 V |
| Rated frequency | 50/60 Hz |
| Degree of protection | IP20 |
| Width in number of modular intervals | 2 |
Performance and Safety
| Feature | Value |
|---|---|
| Rated extreme short-circuit capacity | 10 kA |
| Rated conditional short-circuit current | 10 kA |
| Rated service short-circuit capacity | 7.5 kA |
| Impulse withstand voltage | 4 kV |
| Dielectric proof voltage | 2 kV |
| Power loss | 5,04W |
| Energy limitation class | 3 |
| Electrical resistance | 10000 cycles |
| Mechanical resistance | 20000 cycles |
| Overvoltage category | III |
Installation
| Feature | Value |
|---|---|
| Tightening torque | 4 N-m |
| Mounting type | DIN-Rail |
| Ambient temperature | -25/+55 degrees |
| Contact position indication | Red ON / Green OFF |
| Cable stripping length | 11 mm |
| Pollution degree | 2 |
Dimensions
| Feature | Value |
|---|---|
| Width | 36 mm |
| Height | 86 mm |
| Depth | 72 mm |
Data sheet
- Modules: 2
- Poles: 2P
- Curve: C
- Breaking capacity: 6KA
- RCD Type: A
- Differential current : 0.3A
- Amps: 20A